FP200 Gold and fire resistant cables from Prysmian Cables UK
Manufacturing experience
The manufacturer shall have at least 10 years experience in the supply of fire resistant cables of similar construction.Certification
The fire resistant properties of the cable shall be certified by a recognised approval body.Sheath
The sheath shall be a robust mineral filled compound complying with BS7655 Type LTS3.Screen
The screen shall consist of a longitudinally applied laminated aluminium tape, of minimum metal thickness 0.075mm, securely bonded to the sheath.Core Identification
Cores shall be identified by colours.Insulation
The insulation shall be of a robust cross-linked mineral filled type complying with BS7655 type EI5.Conductors
Conductors shall consist of plain annealed copper and the circuit protective conductor of tinned annealed copper.Voltage rating
The cables shall be rated at 300/500V
General
Cables for surface wiring of fire alarm and emergency lighting systems should be of screened construction and sufficiently robust to meet the intended installation condition.