Enhanced Fire Resistant Wiring Cable
> 300/500V
> BS 7629-1
> BS EN 50200 PH30, PH60 & PH120
> BS EN 50200+Annex E
> BS 8434-2
> BS 8519 control circuits
> BASEC Approved
> LPCB Approved
> Low smoke, zero halogen, flame retardant
FP PLUS Model Specification
General
Cables for fire detection and fire alarm critical signal paths in enhanced application areas, voice alarm systems and emergency lighting systems should be of screened construction and sufficiently robust to meet the intended installation condition.
Manufacturing experience
Cables should meet the performance requirements of BS6387 Category CWZ, EN 50200 PH120, BS 8434-2 120 minutes, BS EN 60332-1-2, BS EN 50266-2-4, BS EN 61034-2 and produce less than 0.5% acidic gases when tested in accordance with BS EN 50267-2-1.The manufacturer shall have at least 10 years experience in the supply of fire resistant cables of similar construction.
Certification
The fire resistant properties of the cable shall be certified by a recognised approval body.
Sheath
The sheath shall be a robust mineral filled compound complying with BS7655 Type LTS3.
Screen
The screen shall consist of a longitudinally applied laminated aluminium tape securely bonded to the sheath.
A full size uninsulated tinned copper circuit protective conductor shall be in contact with the screen.
Core Identification
Cores shall be identified by colours.
Insulation
The insulation shall be of a robust cross-linked mineral filled type complying with BS7655 type EI5.
Conductors
Conductors shall consist of plain annealed copper and the circuit protective conductor of tinned annealed copper.
Voltage rating
The cables shall be rated at 300/500V
FP250 Fire Performance Gland
The fire performance gland is a nylon cable gland which is the optimum choice for fire alarm cables.
•Easy fit gland
•One size fits a range of cables
•Available in red or white to match the cable
FP Firefix Single Clip
The Single Clip Firefix is an LUL Approved clip for rapid installation of fire alarm and emergency lighting cables.
Features and Benefits
•LUL APR Product ID 1960.
•The Firefix™ system is fast easy and meets the cable support requirements of
•British standards: BS5839-1: 2002, BS5266-1:2011 and BS5839-8: 2006.
•Made from corrosion resistant Stainless Steel which is coated with an intumescent LSOH coating in either white or red to match the cable.
•Can be fixed to steel, block work, composite steel decking, brick or concrete.
FP Firefix Double Clip
The double clip Firefix is an LUL approved clip for rapid installation of fire alarm and emergency lighting cables.
Features and Benefits:
•LUL APR Product ID 1960.
•The Firefix™ system is fast easy and meets the cable support requirement of British standards: BS5839-1: 2002, BS5266-1:2011 and BS5839-8: 2006.
•Made from corrosion resistant Stainless Steel which is coated with an intumescent LSOH coating in either white or red to match the cable.
•Can be fixed to steel, block work, composite steel decking, brick or concrete.