FP200 Gold – Model Specification

Manufacturing experience

The manufacturer shall have at least 10 years experience in the supply of fire resistant cables of similar construction.

Certification

The fire resistant properties of the cable shall be certified by a recognised approval body.

Sheath

The sheath shall be a robust mineral filled compound complying with BS7655 Type LTS3.

Screen

The screen shall consist of a longitudinally applied laminated aluminium tape, of minimum metal thickness 0.075mm, securely bonded to the sheath.

An uninsulated tinned copper circuit protective conductor shall be in contact with the screen.

Core Identification

Cores shall be identified by colours.

Insulation

The insulation shall be of a robust cross-linked mineral filled type complying with BS7655 type EI5.

Conductors

Conductors shall consist of plain annealed copper and the circuit protective conductor of tinned annealed copper.

Voltage rating

The cables shall be rated at 300/500V

General

Cables for surface wiring of fire alarm and emergency lighting systems should be of screened construction and sufficiently robust to meet the intended installation condition.

Cables should meet the performance requirements of BS6387 Category CWZ, EN 50200 PH30 & PH60, BS 8434-1 30 minutes, BS EN 60332-1-2, BS EN 50266-2-4, BS EN 61034-2 and produce less than 0.5% acidic gases when tested in accordance with BS EN 50267-2-1.
FP News
Prysmian cables help protect water plants on the Isles of Scilly
Prysmian cables help protect water plants on the Isles of Scilly

Read More

View all >
FP Updates
BS5266 Guide
A guide to the selection of cable types for particular building applications
VIew all >
FP Stockists
stockist
Stockist Locator >