Fire Resistant Conduit Wiring Cable
> 450/750V
> BS6387 Category C,W & Z*
> BS EN 50200 PH30, PH60 and PH120*
> BS EN 50200+Annex E*
> BS8434-2*
> Use in steel conduit to achieve fire rating
> LPCB Approved
> Low smoke, zero halogen, flame retardant
FP100 Model Specification
General
Single core cables for fire alarm systems, emergency lighting and other essential services required to operate in the event of fire, which are required to be installed in conduit or closed trunking should be of a fire resistant construction complying with the requirements given below, so as to form a fire and mechanical damage resistant system. Where the conduit or trunking is not buried in the structure of the building it should be of metallic construction.
Manufacturing Expense
The manufacturer shall have at least 10 years experience in the supply of fire resistant cables of similar construction.
Certification
The fire resistant properties of the cable shall be certified by a recognised approval body.
Core Identification
The cables shall be identified by colours.
Insulation
The insulation shall be of a robust cross-linked mineral filled type complying with BS7655 type EI5. The thickness shall comply with BS7211. A mineral ceramic fire resistant tape shall be applied over the conductor to meet the fire resistance test requirements.
Voltage rating
The cables shall be rated at a minimum 450/750V.